Calculation method and use
Evaluates water-pipe head loss, flow or diameter relationships with the empirical Hazen-Williams equation.

Estimate head loss in pressurized water pipes from flow, diameter, length and Hazen-Williams C coefficient.
Calculate head loss, flow rate or approximate required inside diameter for pressurized water pipelines using the Hazen–Williams equation.
The Hazen–Williams C coefficient varies with pipe material, age, lining and operating condition. Defaults are for preliminary estimates; use manufacturer/authority data and actual inside diameter for final design.
Evaluates water-pipe head loss, flow or diameter relationships with the empirical Hazen-Williams equation.
An empirical coefficient representing hydraulic smoothness of the pipe.
It is most commonly applied to water distribution and conveyance systems.
For the same flow, friction head loss decreases strongly as diameter increases.
A higher C represents a hydraulically smoother pipe and produces lower calculated friction loss for the same flow and diameter. These ranges are useful for preliminary comparison; pipe age, lining condition and manufacturer or authority data should govern final design.
| Pipe / condition | Typical C | Design note |
|---|---|---|
| New PVC / HDPE / GRP | ≈ 140–150 | Smooth new internal surface |
| Cement-mortar-lined ductile iron | ≈ 130–140 | Verify lining condition |
| New steel | ≈ 120–140 | Internal coating matters |
| Concrete | ≈ 110–130 | Surface condition and age matter |
| Older steel / cast iron | ≈ 80–120 | Aging and deposits may increase loss |
C is not a permanent material constant. Select it for the actual internal condition and design life of the pipe.
This comparison holds flow, length and C constant and changes only internal diameter. Because diameter appears with an exponent of about 4.87, a modest increase in diameter can sharply reduce friction head loss.
Illustrative comparison at approximately 317 GPM (20 L/s), 3,281 ft (1,000 m) and C=140.
Consider approximately 317 GPM (20 L/s) through a 6 in (150 mm) internal-diameter pipe over 3,281 ft (1,000 m), using C=140.
For pump-system head, add static elevation difference and applicable minor losses from valves, bends, tees and fittings rather than treating Hazen–Williams friction as the total dynamic head by itself.
For the same flow, 6 in (150 mm) diameter and 3,281 ft (1,000 m) length, calculated friction loss rises as C falls: about 24.0 ft (7.31 m) at C=150, 27.3 ft (8.31 m) at C=140, 36.3 ft (11.05 m) at C=120 and 50.8 ft (15.49 m) at C=100. Using a new-pipe C for an aged line can therefore understate expected friction loss.